Number of RRH |
|
up to 6 RRH |
Compatible with MASTERLINE Classic Hybrid |
|
up to 12 fibers and up to 12 power wires |
Box dimensions |
|
429 × 390 × 159 mm |
U(N) rated voltage |
|
−48 V DC |
I(N) rated current per RRH |
without circuit breaker
with circuit breaker |
15.0 A
11.7 A |
Ambient temperature range |
operation
installation |
−40 to +75 °C (with CB +55 °C)
−10 to +50 °C |
Box material |
|
glass-filled polycarbonate |
Ingress protection |
|
IP67 |
Impact resistance |
|
IK 07 (EN 62262) |
Colour |
|
RAL 7035 grey |
Halogen free |
|
IEC 60754-2 |
UV resistant for outdoor use |
|
ISO 4892-3 |
Material flammability rating |
|
UL94-V0 |
Screw terminals |
cable entry |
6 mm2 to 16 mm2 (25 mm2 without wire end sleeves) |
|
cable exit |
4 mm2 to 6 mm2 |
Circuit breaker (optional) |
|
miniature circuit breaker C 20A, type 5SY6120-7 |
Surge protection device (optional) |
|
SPD type 1+2/class I+II or type 2/class II |